Free HVAC tool · room by room

HVAC Duct Size Calculator (room by room)

Enter each room's CFM (or sq ft for an estimate). Get every branch size, total airflow and the main trunk — free, no sign-up.

✓ Formulas and limits cited below✓ No sign-up✓ Nothing stored

FLOOR 2FLOOR 1BASEMENTRETURNFILTERFURNACEOUTDOOR UNITLINE SETSUPPLY TRUNKDucty: return side checked ✓

Supply Return

1 Rooms enter CFM or sq ft per room
Settings · 0.08 in.wc/100 ft · sheet metal · round + rect 8″

Material: sheet metal only. Flex: use the manufacturer's friction chart.

RoomInputValueResult (round · rect · CFM · FPM)Remove
CFM7″ round (needs 6.1″) · 6×8″ · 100 CFM · 374 FPM ✓
2 Branches & trunk

    Estimate only — not a Manual J / Manual D design. Flex: use the manufacturer's friction chart. How we calculate ↓ · Try a 6-room example

    Duct Sizing Chart: CFM to Round Duct Size

    Sheet metal, round, rounded up to standard sizes (4–10, 12, 14 … 24″); small number = velocity, FPM. Generated by formula F3 with the same rules as the calculator: up to 600 CFM sized as a branch (one size up above 600 FPM), 800 CFM and more as a trunk (one size up above 700 FPM).

    CFMFR 0.06FR 0.08FR 0.10
    505″ 3675″ 3675″ 367
    756″ 3826″ 3826″ 382
    1007″ 3747″ 3746″ 509
    1508″ 4308″ 4307″ 561
    2009″ 4538″ 5738″ 573
    25010″ 4589″ 5669″ 566
    30010″ 55010″ 55010″ 550
    40012″ 50912″ 50912″ 509
    50014″ 46814″ 46814″ 468
    60014″ 56114″ 56114″ 561
    800 trunk16″ 57316″ 57316″ 573
    1000 trunk18″ 56618″ 56616″ 716
    1200 trunk18″ 67918″ 67918″ 679
    1500 trunk20″ 68820″ 68820″ 688
    2000 trunk24″ 63722″ 75822″ 758

    Room CFM Calculator: How Many CFM per Square Foot

    Switch a room's input to sq ft to estimate its CFM. By default the calculator uses 1 CFM per sq ft; if you enter the system size in tons, it splits 400 CFM per ton across the rooms by floor area. Either way it is an estimate, not a Manual J load calculation — see the FAQ below.

    How to size ductwork for a house

    1. Get room loads (Manual J).
    2. Fan CFM from the equipment data (≈350–400 CFM/ton as a sanity check).
    3. Split CFM by room load (F7).
    4. Friction rate = available static pressure × 100 ÷ total effective length (F5).
    5. Check velocity: branches ≈600 FPM recommended (900 max), trunk ≈700 recommended (900 max).

    Duct Size Formula (Friction Rate Method)

    Δh = 0.109136·q^1.9 / De^5.02 (Engineering ToolBox) · De = 1.30·(ab)^0.625/(a+b)^0.25 · FR = ASP·100/TEL (ACCA)

    The velocity check bumps the size up by one standard step only, so a result can still be above the recommended velocity; the calculator flags anything over 900 FPM.

    FAQ

    What duct size do I need?

    It depends on the room's airflow (CFM) and the design friction rate. Size the duct by friction first, then check air velocity and go up a size if it is too fast. Example: 144 CFM at 0.08 in.wc/100 ft needs 6.98″, so a 7″ round duct, at about 539 FPM — under the 600 FPM recommended for supply branches.

    Sources: engineeringtoolbox.com, ahrinet.org

    What size duct for a 12x12 room?

    There is no fixed number per room size. In ACCA Manual D, each room's design CFM is the system fan airflow split in proportion to that room's heating and cooling load from Manual J. Get the room load first, then enter its CFM here. The sq ft mode of this calculator is only a rough estimate. If you already know the room's CFM, the chart above gives the size: for example, about 100 CFM is a 7″ round duct at 0.08 in.wc/100 ft (6″ at 0.10).

    Sources: ahrinet.org

    How many CFM will a 14x8 duct carry?

    A 14×8″ duct has an equivalent round diameter of 11.46″. At a friction rate of 0.08 in.wc/100 ft that is about 534 CFM; at 0.10 about 600 CFM. By velocity: its area is 0.778 sq ft, so 467 CFM at 600 FPM and 544 CFM at 700 FPM.

    Sources: engineeringtoolbox.com, engineeringtoolbox.com, ahrinet.org

    How much CFM can a 12x12 duct carry?

    A 12×12″ duct equals a 13.12″ round duct. At 0.08 in.wc/100 ft it carries about 763 CFM, at 0.10 about 858 CFM. Its area is 1 sq ft, so at the 700 FPM recommended for supply trunks it moves 700 CFM, which is the tighter limit.

    Sources: engineeringtoolbox.com, engineeringtoolbox.com, ahrinet.org

    How many CFM is a 12x24 duct?

    A 12×24″ duct equals an 18.28″ round duct, about 1,834 CFM at 0.08 in.wc/100 ft. But its area is 2 sq ft, so 1,834 CFM means about 917 FPM — above the 900 FPM maximum. Limited by velocity it carries 1,400 CFM at 700 FPM or 1,800 CFM at 900 FPM.

    Sources: engineeringtoolbox.com, engineeringtoolbox.com, ahrinet.org

    What duct size for 800 CFM?

    At 0.08 in.wc/100 ft the friction method gives 13.4″, but air would move at about 822 FPM, above the 700 FPM recommended for a supply trunk. Keeping 700 FPM needs about 14.5″, so a standard 16″ round. A 14″ duct is fine if you accept up to 900 FPM (the maximum).

    Sources: engineeringtoolbox.com, ahrinet.org

    What size duct for 5000 CFM?

    5,000 CFM is commercial scale, outside residential Manual D. For reference only: friction at 0.08 gives 26.7″ round at about 1,284 FPM, far above limits; 900 FPM needs about 31.9″ and 700 FPM about 36.2″. Have an engineer design it.

    Sources: engineeringtoolbox.com, ahrinet.org

    What is the 2 foot rule for ductwork?

    After any change in airflow — an elbow, transition or takeoff — air needs 18 to 24 inches to re-pressurize. So space branch takeoffs about 24″ apart, keep them about 24″ from elbows and transitions, and never put an outlet in the end cap: place it two feet before the end.

    Sources: hvactoday.com

    How many CFM per ton?

    The conventional target is 400 CFM per ton (12,000 BTU/h). DOE Building America notes that higher-efficiency homes and equipment often land closer to 350 CFM per ton. Building Science Corporation gives 350–400 CFM/ton for humid climates and 400–425 for dry ones. Use the manufacturer's fan data for the real number.

    Sources: eere.energy.gov, buildingscience.com

    How many CFM per square foot?

    No ACCA or DOE source gives a fixed CFM per square foot; airflow follows the room's heating and cooling load (Manual J), not its floor area. Per-square-foot figures are rules of thumb. That is why this calculator labels sq ft results as an estimate and lets you edit the factor.

    Sources: ahrinet.org, eere.energy.gov

    What size return air duct do I need?

    Return ducts carry the same total airflow as the supply side. Building America guidance suggests sizing return capacity generously, keeping return air velocity under 500 FPM, and sizing the grille's net free area at 1.5× the return duct's cross-section. Use at least one central return per floor, ducted back to the air handler, and give closed bedrooms a transfer grille or jump duct.

    Sources: energy.gov, basc.pnnl.gov

    What size duct for a 3 ton unit?

    At the conventional 400 CFM per ton, 3 tons is about 1,200 CFM (about 1,050 CFM at 350 CFM/ton). From the chart above, 1,200 CFM is an 18″ round main trunk at 0.08 in.wc/100 ft (about 679 FPM). Check the manufacturer's fan data for real airflow.

    Sources: eere.energy.gov

    What are standard round duct sizes?

    This calculator rounds up to 4–10″ in 1″ steps, then 12″ to 24″ in 2″ steps.

    How do I know if my ducts are too small?

    Enter each room's CFM: if a branch or trunk shows a velocity above 900 FPM, the duct is undersized for that airflow.

    Sources: ahrinet.org

    Limits — when to call a pro

    Rules of thumb are not a Manual J load calculation or a Manual D duct design. Call a pro if: you are replacing or resizing equipment (ACCA Manual J and S are the basis, per DOE); rooms are too hot, cold or noisy after a change; the system is above 900 FPM anywhere; you need a permit or code sign-off; or the job is commercial scale (thousands of CFM).

    Sources: eere.energy.gov, ahrinet.org